Search

Allen-Bradley

Allen-Bradley 140G MCCB K Frame Trip Unit 4P 400A Adjustable Thermal Magnetic

Item No. 140GKTF4D40
Product Range: Moulded Case Circuit Breaker
Component Type (ETIM Class)
Power switching circuit breaker
Electrical
Rated current In400 A
Number of poles4
Type of protection trip unitThermal/magnetic release
Trip curveAdj. thermal, adj. magnetic
Frame size rating400 A
Long time overload protection adjustment range280-400 A
Instantaneous protection adjustment range2000-4000 A
Rated frequency50-60 Hz
Rated insulation voltage Ui1000 V
Dimensions
Width186 mm
Environment
Rated surrounding temperature without derating40 °C
Maximum operating temperature75 °C
Storage temperature-40-80 °C
Max. altitude before derating2000 m