- Miniature circuit breaker - Din-T6 series 6 kA MCB,

- Standards AS/NZS 60898, Approval No. N17481,

- Current range 2-63 Amps 1, 2 and 3 pole,

- Sealable and lockable handle,

- Available in curve type C and D,

- Mounts on NC or CD chassis,

- Padlockable in off position, 6kA, 10kA & 15kA short circuit breaking capacities available, 50kA and 65kA fuse backup,

- On and Off indication with colour coding,

- Handle can be sealed and locked in "on" or "off" position,

- R19High speed operation and rapid arc quenching,

- Consistant line and load terminal height for Din-T 6, 10 & 15 MCB's, IP20 finger protection,

- 35mm2 capacity terminals,

- Wide range of accessories,

- Conformity to Australian and International standards,

- Versatility in mounting, distribution boards, switchgear panels and consumer units,

- High selectivity figures, Information clearly labeled on front of breaker,

- Elimates confusion regarding the operating state of the MCB,

- Increased protection as contacts open through overload or short circuit even when handle is sealed in the "on" position,

- Saves cost, allows for a fuseless system and confines power outages to the effected circuit preventing wide spread loss of power,

- Can fit larger cables,

- Provides greater flexibilty of use,

- Security on conformitiy,

- Special data very accessible,

- The LINE side is the "OFF" (bottom) side of the MCB,

- Module width = 18mm, Suits CD style chassis,

- Suitable for use with the DSRCM range of add-on RCD modules,

- Din-T6 MCBs are compatable with the ICL & IBC range of buscomb.

- Nominal current: 6 A

- Number of poles: 1

- Short circuit capacity 6 kA: 240 V AC

- Short circuit: 20 kA

- Maximum voltage (DC): 48 V

- Use at DC: When using Din-T6 in a DC application the magnetic tripping current is approximately 40 % higher than in AC 50/60 Hz.

- Shock resistance (In X, Y, Z directions): 20 g with shock duration 10 ms (minimum 18 shocks), 40 g with shock duration 5 ms (minimum 18 shocks)

- Vibration resistance (In X, Y, Z directions): 3 g in frequency range 10 to 55 Hz (operating time at least 30 min). According to IEC 60068-2-6

- Storage temperature: From -55 °C to +55 °C, according to IEC 88 part 2 - 1 (duration 96 hours)

- Operating temperature: From -25 °C to +55 °C, according to VDE 0664 parts 1 and 2

- Use at 400 Hz: At 400 Hz the magnetic trip current is approximately 50 % higher than in AC 50/60 Hz